Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by gabbasin: 12:33pm On Sep 25, 2019
Can a 5000VA stabilizer carry 2 nos of 1hp (horsepower) air conditions? Please I need professional advice
Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by pakingzzzzz(m): 10:40pm On Sep 26, 2019
gabbasin:
Can a 5000VA stabilizer carry 2 nos of 1hp (horsepower) air conditions? Please I need professional advice
500va is also 5000watts.
1hp=740watts.
2hp=1480watts.
But electricity don't like to be judged that way. It gets notirious when you are dealing with motor.
So, you will want to add a head room of about 250watts.
This implies, 2hp= 1980watts.
Then there is the start up current required to run a motor. Every motor wants to take three times it's rated power when switched on. So a 1hp motor would want to draw around 2500watts when switched on momentarily. But it will normalise within seconds.
Your 5000va can power the 2hp air conditioning.

6 Likes

Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by QuickStandard: 6:18am On Sep 27, 2019
Yes it can
Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by gabbasin: 7:22am On Sep 27, 2019
pakingzzzzz:

500va is also 5000watts.
1hp=740watts.
2hp=1480watts.
But electricity don't like to be judged that way. It gets notirious when you are dealing with motor.
So, you will want to add a head room of about 250watts.
This implies, 2hp= 1980watts.
Then there is the start up current required to run a motor. Every motor wants to take three times it's rated power when switched on. So a 1hp motor would want to draw around 2500watts when switched on momentarily. But it will normalise within seconds.
Your 5000va can power the 2hp air conditioning.
thanks
Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by cassette(m): 3:33am On Aug 09, 2021
[quote author=pakingzzzzz post=82600248]
500va is also 5000watts.
1hp=740watts.
2hp=1480watts.
But electricity don't like to be judged that way. It gets notirious when you are dealing with motor.
So, you will want to add a head room of about 250watts.
This implies, 2hp= 1980watts.
Then there is the start up current required to run a motor. Every motor wants to take three times it's rated power when switched on. So a 1hp motor would want to draw around 2500watts when switched on momentarily. But it will normalise within seconds.
Your 5000va can power the 2hp air conditioning.
[/
Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by Dat2jo: 11:14pm On Mar 02, 2022
pakingzzzzz:

500va is also 5000watts.
1hp=740watts.
2hp=1480watts.
But electricity don't like to be judged that way. It gets notirious when you are dealing with motor.
So, you will want to add a head room of about 250watts.
This implies, 2hp= 1980watts.
Then there is the start up current required to run a motor. Every motor wants to take three times it's rated power when switched on. So a 1hp motor would want to draw around 2500watts when switched on momentarily. But it will normalise within seconds.
Your 5000va can power the 2hp air conditioning.
Bro, Century 2kva wall stabilizer claims on the carton that it can power a 1.5hp AC. How true Sir?
Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by pakingzzzzz(m): 8:21pm On Apr 16, 2022
Dat2jo:
Bro, Century 2kva wall stabilizer claims on the carton that it can power a 1.5hp AC. How true Sir?

Yes it can.. We the the new generation split unit and microprocessor driven motor. The tend to do "soft start" on the motors.
This soft start gets the motor gently turning, but not enough to cause it to want to pull the maximum times three current during start up

2 Likes

Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by Dat2jo: 7:39pm On Apr 17, 2022
pakingzzzzz:


Yes it can.. We the the new generation split unit and microprocessor driven motor. The tend to do "soft start" on the motors.
This soft start gets the motor gently turning, but not enough to cause it to want to pull the maximum times three current during start up
Thanks for the explanation bro
Re: Can A 5000VA Stabilizer Carry 2 1hp Air-conditioners by sylve11: 2:38pm On Dec 13, 2022
pakingzzzzz:

500va is also 5000 watts.
1hp=740watts.
2hp=1480watts.
But electricity doesn't like to be judged that way. It gets notorious when you are dealing with the motor.
So, you will want to add a headroom of about 250 watts.
This implies, 2hp= 1980watts.
Then there is the start-up current required to run a motor. Every motor wants to take three times its rated power when switched on. So a 1hp motor would want to draw around 2500 watts when switched on momentarily. But it will normalise within seconds.
Your 5000va can power the 2hp air conditioning.

Perfectly explained. cool

1 Like

(1) (Reply)

How To Use Nairabet Computer/pc Version On Mobile Phone / USING UPS AS INVERTER 24HRS / First Water-only Powered Generator You Can Buy

(Go Up)

Sections: politics (1) business autos (1) jobs (1) career education (1) romance computers phones travel sports fashion health
religion celebs tv-movies music-radio literature webmasters programming techmarket

Links: (1) (2) (3) (4) (5) (6) (7) (8) (9) (10)

Nairaland - Copyright © 2005 - 2024 Oluwaseun Osewa. All rights reserved. See How To Advertise. 18
Disclaimer: Every Nairaland member is solely responsible for anything that he/she posts or uploads on Nairaland.