| Re: Solar Energy, A Complement To FTA by ceejay80s(m): 11:11am On May 29 |
Trippledots:me too |
| Re: Solar Energy, A Complement To FTA by adrusa: 11:11am On May 29 |
AyobamiOluwole:Interesting. The easy recourse to insult by children who have more data than sense has also crept here. You asked a silly question, but I chose to respond to you with education and your erudite response is I'm blabbing! ![]() |
| Re: Solar Energy, A Complement To FTA by Collione: 11:15am On May 29 |
Hello house. I have a 6kw deye hybrid inverter the plastic body that's trending. Anyways the PV port seems to be outputting AC current somehow. If you put your tester in the port it illuminates and if you connect the PV breaker to the SPD and then earth the SPD my inverter and appliances will be shocking. How can I solve this . Is the inverter having factory issues? |
| Re: Solar Energy, A Complement To FTA by adrusa: 11:30am On May 29 |
Valto:Your response is very interesting and deliberately misleading. It is not everyone that is an expert on the poor ethics of sachet inverter manufacturers that will recognize that a 3000W inverter actually means 1500W. I'm familiar with inverters and even I don't understand a system that inflates inverter powers using their short-lived peak output. That was why I asked you. And I expected that you will respond with their true nominal powers, not hiding under this "manufacturers' claims". Even Aliexpress sellers clearly indicate the nominal ratings of their inverters, not just leave it to buyers to guess. This is an example from Aliexpress: [/b]Warm reminder: Dear buyer! Inverter 2000W, continuous power is 900W, peak power is 2000W. Inverter 3000W, continuous power is 1300W, peak power is 3000W. Inverter 4000W, continuous power is 1600W, peak power is 4000W. Inverter 5000W, continuous power is 2200W, peak power is 5000W. Inverter 6000W, continuous power is 2500W, peak power is 6000W. Inverter 8000W, continuous power is 3000W, peak power is 8000W.[b] When you advertise your inverters next time, please do the same. Include their real nominal outputs so that buyers know exactly what they are getting. It is the honest thing to do. And as you can see, real power is not always "half of their rated powers", it is often less than half. |
| Re: Solar Energy, A Complement To FTA by bassdow: 11:36am On May 29 |
Valto:Would say Not everyOne is aware they all are rated at PEAK but funny enbough, if you decide going the extra mile to point those out and your words becomes length, dem go call am epistle. Now e short, dem still complain. MoreOver, marketingWise, trust ain't to be expected always |
| Re: Solar Energy, A Complement To FTA by bassdow: 11:41am On May 29*. Modified: 12:17pm On May 29 |
Topper33:Honestly, you really can't say which is better qualityWise until you get idea of quality of cells used. Hopefully quality of the Cells of your custom built pack is better else it would be very painFool. A lot of times, we tend to priotize LOWest Price because wouldn't be surprised said battery didn't wasn't from @Valto or @mrReed you patronized. |
| Re: Solar Energy, A Complement To FTA by eghos12(m): 11:47am On May 29 |
adrusa:Many a time, it is common knowledge that the buyers are already used to the Chinese terminology in how they brand their product. Hence people that buy from him are already in the game. they want to get theirs quickly without wating for AliExpress delivery time. |
| Re: Solar Energy, A Complement To FTA by AyarmBoye(m): 11:48am On May 29 |
adrusa:oga rest abeg,,if you have complaints reach the manufacturers and not @valto the reseller….or go to Aliexpress and order…Or just go into the business and advertise your own like that….You just Dey type type type on top sachet inverter wey no get value |
| Re: Solar Energy, A Complement To FTA by bassdow: 11:50am On May 29 |
Collione:There's defintely leakAge somewhere. A technician could assist with that. Also you didn't inform us if said inverter is connected to Grid (NEPA / PHCN), neither did you inform us if said system is earthed. |
| Re: Solar Energy, A Complement To FTA by adrusa: 12:22pm On May 29 |
AyarmBoye:Even if it is only one person who is saved from buying 2500W inverter while thinking that they were buying 6000W, my job would have been done. It costs nothing to be totally upfront with a customer who may not be familiar with the fraudulent ratings practice by the Chinese. I will never buy an inverter without knowing the real power ratings even if they are inflated by the manufacturers using Peak power to advertise it. By the way, keep the insults coming, it tells me the kind of persons you are. |
| Re: Solar Energy, A Complement To FTA by adrusa: 12:25pm On May 29 |
Collione:Disconnect the AC output and see if your tester is still illuminating. Ensure that the misconnection is not coming from your house wiring before technicians start playing with your inverter. |
| Re: Solar Energy, A Complement To FTA by AyobamiOluwole: 12:41pm On May 29 |
adrusa:Oga all this your English is unnecessary. Go and rest. You have no point. |
| Re: Solar Energy, A Complement To FTA by AyarmBoye(m): 12:47pm On May 29 |
adrusa:I didn’t insult you boss..apologies if it sounded like that…I just think sachet inverters aren’t worth the stress… |
| Re: Solar Energy, A Complement To FTA by Unfaized: 12:58pm On May 29 |
adrusa:It's your job to do some research then. Almost all satchet inverter buyers are aware of this fact. If you don't know then you probably shouldn't be buying one. You can politely ask questions to learn, but accusing someone of false advertising on something that is common knowledge doesn't make you sound as smart as you think. If by page 2,374 you still dey blow big grammar on this topic then what you need is research & education on the topic, not claims. The pricing alone suppose trigger your curiosity. |
| Re: Solar Energy, A Complement To FTA by Collione: 1:02pm On May 29 |
bassdow:Thanks for your feedback it's connected to the grid but even with grid absent and this is at night it still shocks. The inverter is earthed. From the pv port on the body of the inverter with a tester you will see the AC current flowing. Once the SPD is connected and earthed everything will start shocking. I suspect the current leaks from the pv port to the SPD and to the earthing wire which causes the shock. The house is earthed but the way. |
| Re: Solar Energy, A Complement To FTA by Collione: 1:03pm On May 29 |
adrusa:This test was done but no changes. It's frustrating because asides from the shocking everything else works perfectly |
| Re: Solar Energy, A Complement To FTA by bassdow: 1:20pm On May 29 |
Collione:one thing I would suggest is your technician should do a thorough check to spot where issue is coming from. Who knows, could even be from your inverter sef as transformerLess inverters lack the issolation that transformer based inverters have. Another is, is the earthing properly done ? At end of the day, it's easier for those with physical access to spot the issue than the gueses we doing here |
| Re: Solar Energy, A Complement To FTA by Tdoctor(m): 2:09pm On May 29 |
Unfaized:I don't think we should assume that all sachet buyers know that the inverters are rated at their peak power. As a user, if not for this forum, I believed that all inverters were rated at their continuous power. That is why I am afraid of installers - they are used to not telling clients the truth about many things. Users want to know things like peak power, continuous power, SOC, etc. These things help you to manage your installation well. My two cents. |
| Re: Solar Energy, A Complement To FTA by Valto(m): 2:21pm On May 29 |
adrusa:anybody that enters my dm to place order, already knows or is made to know that the real power is half! check my jiji page ,it is the same info. i am not the producer,neither do i change the label in Nigerian , the ones in aliexpress are labelled the same in peak! |
| Re: Solar Energy, A Complement To FTA by kuss: 3:00pm On May 29 |
AyarmBoye:I tire ooo Satchet inverters that are disposables |
| Re: Solar Energy, A Complement To FTA by Valto(m): 3:18pm On May 29 |
Valto:example
|
| Re: Solar Energy, A Complement To FTA by AyobamiOluwole: 3:44pm On May 29 |
Valto:Lols. See Valto o. You Dey shalaye? You really get time for that ITK. Nor mind that guy. |
| Re: Solar Energy, A Complement To FTA by Fremlin: 4:06pm On May 29 |
AyobamiOluwole:Oga rest na No be everybody be expert like you. Allow other learn abeg |
| Re: Solar Energy, A Complement To FTA by dollarnaira(m): 6:34pm On May 29 |
You guys should leave satchet inverter users alone. Go to China to change what had been a fact if you don't like the label --- @adrusa. Hybrid labels cannot be the same as satchet inverters. Hybrid is labelled as continuous Satchet is labelled as peak. Don't wait for installers to tell you everything. All that is needed is the ability to read English or use Google translate to understand Chinese labels. |
| Re: Solar Energy, A Complement To FTA by Tdoctor(m): 6:49pm On May 29 |
Nothing will spoil if we explain the difference between sachet and hybrid inverter power differences to people. Experts can be arrogant at times. |
| Re: Solar Energy, A Complement To FTA by dollarnaira(m): 7:18pm On May 29 |
Tdoctor:Goto WhatsApp AI you will learn and become a pro . Just type it in finish as you don't need to wait for anyone. E no hard na... |
| Re: Solar Energy, A Complement To FTA by justasitis: 7:23pm On May 29 |
Collione:1. Check the SPD linked to PV from panel to ensure that it’s not AC SPD that’s used in place of DC SPD. 2. Check and also test the AC output wires from the inverter to ensure that live and neutral were not interchanged. 3. Check and also test the AC input wires to the inverter to ensure that live and neutral wires were not interchanged. |
| Re: Solar Energy, A Complement To FTA by Bryanluke: 7:36pm On May 29 |
Pls someone should recommend the best PWM charge controller to buy to be used for a Lithium ion battery cells |
| Re: Solar Energy, A Complement To FTA by bassdow: 8:16pm On May 29 |
Tdoctor:Bros leave them; they know that many (most) people don't know this things AND it's to their (technicians / sellers / installers) advantage. When working with clients, I go chat with them so tey e go be like say na them dey give instructions BUT guess what, deep down I know those making millions in the business don't talk much. In fact a lot wouldn't take a client serious if said customer decides buying things themSelves. Ask question anyHow and they begin vex. Oooh you (customer) seem to have some idea of the project, they (installers/engineers) hate it. |
| Re: Solar Energy, A Complement To FTA by bassdow: 8:19pm On May 29 |
Bryanluke:Why PWM and not MPPT Also when you say "BEST" , hope you're aware that word is relative. Either way, let me respond accordingly, buy from the likes of morningStar, epEver, etc. They have good PWM charge controllers |