| Re: Solar Energy, A Complement To FTA by lexi28(m): 9:28pm On Jun 08, 2018 |
NiyiOmoIyunade:sir, you are a born tutor! awesome. I love this oasis of knowledge all can benefit from. |
| Re: Solar Energy, A Complement To FTA by godspeed: 10:29pm On Jun 08, 2018 |
Hello house, I just installed solar panels in my apartment as there is no electricity where I am presently. The solar panels output is 500 watts and I use a luminous tubular battery of 220 ah (12v)with a luminous Inverter of 1000 watts. My power consumption is as FF TV. 135 watts Decoder. 500maH Bulb. 5v The issue is that the battery does not last for more than 2 hours at night even when the sun is hot throughout the day. Note that I don't use it at daytime as I'm always at work. Pls what could be the issue and possible solutions |
| Re: Solar Energy, A Complement To FTA by EnigmaticEnigma(m): 10:31pm On Jun 08, 2018 |
bigrovar: |
| Re: Solar Energy, A Complement To FTA by ebocoms: 10:32pm On Jun 08, 2018 |
Thanks @dapsyra dapsyra: |
| Re: Solar Energy, A Complement To FTA by pranil(m): 11:55pm On Jun 08, 2018*. Modified: 12:51am On Jun 09, 2018 |
NiyiOmoIyunade: Dont even start - If I have to list the spare materials, PCB, cables, sleeves, screws, display meters , MCB's boxes , various tools - I will need 2 to 3 pages . The other day I asked the security guy and gardner to help me only sort and store the extra material accumulated over the last one year and it tool good 5 to 6 hours to sort and label them |
| Re: Solar Energy, A Complement To FTA by pranil(m): 12:04am On Jun 09, 2018 |
NiyiOmoIyunade:I would say now you have reached a level where you should be seriously thinking of ESS setup. Becuase at some point, the different logics end of getting complicated and prone to failure or misbehaving unless continuously tweaked (speaking from past experience. ![]() In ESS setup when the AC is available the AC from the grid is only used if the solar is not enough so the system uses exactly the shortfall between solar and demand to keep batteries at 100 % That was one of the main reasons ( along with lithium compatibility) for me to switch to Victron Have a look at this video - Quite long but explains the ESS concept very well https://www.youtube.com/watch?v=tbpQzEZTElI also shown a snapshot of my system in morning note the grid setpoint at 100 watt to avoid export
|
| Re: Solar Energy, A Complement To FTA by pranil(m): 12:34am On Jun 09, 2018 |
lexi28:I beg to differ. T[b]he only way of reliably testing of earth connection is using something called earth megger[/b] https://www.tester.co.uk/megger-det4td2-earth-tester?gclid=CjwKCAjw0ujYBRBDEiwAn7BKtxVskY0Ebjn7_IDanAUeQ2PbLikI69LuLmSiKQYo8X56c5zYl-vlZBoCPHwQAvD_BwE - If the earth is even connected by 1.5 mm2 wire the light bulb will light up or multimeter will show low voltage. The earth is supplied already from the disco in a good installation by neutral grounding and hence neutral will always show low voltage with earth. A good way to check if the Neutral is earthed at home is to switch off NEPA at the entry point ( including neutral) and then measure the inverter output neutral to earth you will be surprised to note that most inverters will show balanced voltage with respect to earth say 110 V ( P to E) and ( 110 N to E) The higher end inverters have a sperate grounding relay which actuates the main relay ( Victron) or auxiliary contact ( SMA. even newer Ipower models) earth to neutral short on the failure of the grid That kind of earth is enough to reliably trip a ELCB ( earth Leakage) circuit breaker but may not be strong enough to sink a lightning surge ( or switching surge typically earth resistance measured ( when isolated from earth bar) should be less than 5 OHMS ( IEEE) , 10 Ohms ( India) 25 ohms ( USA) In layman's terms during lightning strike, the earth can carry several kiloamperes of current and a high resistance path may raise the circuit potential above 1.5 KV where the normal equipment may fail or people can get shocked Also there are two values to be concerned with earth Touch potential and step potential. Both concern with human safety. A weak earth can raise a potential along the earth point potentially shocking people on failure of insulation of the equipment M[i]y advice is to sink one more rod if you are not sure and connect directly to your earth bar with a solid connection without a break - Typically if the property has large generator e.g. 20 KVA and above you can easily trace and use the generator earth rod as most generator companies will sink a Rod close to the generator and connect to neutral and generator body [/i] |
| Re: Solar Energy, A Complement To FTA by pranil(m): 12:50am On Jun 09, 2018 |
NiyiOmoIyunade:Niyi excellent information and painstakingly explained. - I used this meter ( there is even a wireless version) many times. The only thing I would like to add is that the meter has a jumper on the PCB ( called two wire or three wire ) In two-wire the meter supply comes from the battery while in three wire the meter can be powered from separate auxiliary - After connecting the meter if it still remains off take a look at the jumper Also, the meter needs to be reset after batteries are fully charged as part of initial calibration to report AH correctly see attached user manual of a similar meter ( all of them use the same generic chip and work exactly the same) https://drive.google.com/file/d/0B6eOIBrQmTfLUDdUZ3N4MnNGZWM/view?usp=sharing |
| Re: Solar Energy, A Complement To FTA by pranil(m): 1:12am On Jun 09, 2018 |
godspeed:The tubular battery is approximately 2.4 KWh so with inverter efficiency of 80 % you might get 2 KWH ( as No nepa at all ) your inverter is consuming 40-100wh per hour even if not used when there is no sun - check if the inverter has power saver mode and switch is on also, keep in mind that 200 AH battery at 12 V should be used with C10 rate (max 200 watts load or less) anything more and the rated AH will drop as per phuekerts law - see the table below of similar Trojan battery note as you increase load the rated battery capacity falls The minimum I would recommend of one TV +Decoder and few lights for full overnight use is 2 x 200 AH - Anything less and your battery will fail prematurely due to the high rate of charge-discharge if you can give the model no of inverter I can check the efficiency and loss figures for you to better design the system
|
| Re: Solar Energy, A Complement To FTA by DUNKA(m): 2:48am On Jun 09, 2018 |
makavele:Thanks a million |
| Re: Solar Energy, A Complement To FTA by Saipro(m): 6:48am On Jun 09, 2018 |
makavele: |
| Re: Solar Energy, A Complement To FTA by Saipro(m): 6:48am On Jun 09, 2018 |
pranil:This is more than tempting but I think I'd defer on that kinda upgrade for now. You've inspired me to try Victron products and I've quietly begun a collector's quest ... |
| Re: Solar Energy, A Complement To FTA by Saipro(m): 6:54am On Jun 09, 2018 |
pranil:Makes me proud to be a DIYer. I dread listing my solar-related stuff here (I've lots asides solar gadgets too) as some might get truly concerned. |
| Re: Solar Energy, A Complement To FTA by kadorzy(m): 7:16am On Jun 09, 2018*. Modified: 2:45pm On Jun 09, 2018 |
Good day house, A quick one please. When two batteries are connected in parallel I understand the capacity increases but voltage remains same. But my question is while the batteries are being used do the two batteries drain simultaneously or one after the other.? Thanks. |
| Re: Solar Energy, A Complement To FTA by OnePunchMan: 7:58am On Jun 09, 2018 |
hancock: |
| Re: Solar Energy, A Complement To FTA by zeestone99(m): 8:02am On Jun 09, 2018 |
ayinba1:Call/whatapp 08117398294 for enquiries on diff good brands available here... Gracias |
| Re: Solar Energy, A Complement To FTA by godspeed: 9:26am On Jun 09, 2018 |
pranil:Thanks for the detailed explanation My fear is the the battery is not getting a full charge even when the sun is at full blast for more than seven hours and where I'm located, the sun is frying. I said this because when I bought the battery new, I charged with electricity before the first use as advised, and I got an estimated 15 hour use from the full charge. Ever since then,the battery has never lasted for more than 2 hours even though I don't use it at all during the day and I have 500w panels. I don't think my power consumption is even up to the 200w u advised cos my tv + decoder + 5w bulb adds up to just about 150 watts. My fear of adding an additional battery (I have a spare old one that does 3 hrs on a full charge ) is that I'll need more panels to get a full charge which I feel is an unnecessary expense as I .mainly need to power the tv The inverter is luminous eco volt 1050 and the pic is attached together with the charge controller.
|
| Re: Solar Energy, A Complement To FTA by pranil(m): 9:49am On Jun 09, 2018 |
godspeed:15 hours sounds about right for a new battery but never do that with any battery. from a 200 AH battery you should take maximum 50 % which is 1 to 1.2 KWH ( 100 watt 12 hours or 200 watt 5 hours roughly) 1. This inverter has an eco mode if not on pls. switch it on if not on 2. which charge controller you are using? the inverter does not have one 3. You may have continuously starved the battery of a full charge thus reducing the life. - All tubular batteries like to work not more than 30 % -50 % DOD for a good long life. Also they need a complete Bulk charge , absorb, float which may not be possible with your no of panels and load profile 500 watt panels will normally produce between 1.5 to 2 KWH ( assuming everything is perfect, alignment, position, weather) you have two options 1. Occasionally use a generator to top up the batteries when you use them extensively such as weekend 2. reduce your usage to match the battery charging so they reach float every day with comfortable margin say by 4 PM ( I would invest in a cheap voltmeter at the least so that you can monitor your batteries) https://www.aliexpress.com/item/Digital-Voltmeter-DC-Voltage-Panel-Meter-For-6V-12V-24V-Electromobile-Motorcycle-Car-with-Two-wire/32824519194.html - 2.5 USD or better a cheap AH meter - 15 USD https://www.aliexpress.com/item/DC-100A-LCD-Combo-Meter-Voltage-current-KWh-Watt-Panel-Meter-12v-24v-48v-Battery/32672996346.html? |
| Re: Solar Energy, A Complement To FTA by lexi28(m): 11:05am On Jun 09, 2018 |
yes, Mr Pranil. a Mega Tester will be surest way of ensuring earth connections are good. learnt that when testing for groung/earthing connections on TRANSFORMERS. my reply was based on the equipment Mr Niyi had on ground. good update from you. |
| Re: Solar Energy, A Complement To FTA by godspeed: 11:20am On Jun 09, 2018 |
pranil:Thanks boss The battery is still new, bought it two weeks ago On option 2, I don't even use the battery in the afternoon at all as I'm always at work. I only need the battery to work for like four hours when I return home in the evening. Pic of the controller
|
| Re: Solar Energy, A Complement To FTA by bigrovar(m): 1:31pm On Jun 09, 2018 |
godspeed:There in lies the culprits. Roy solar.. Its you again ... Bro your inverter and solar charge controller have conspired to murder your battery. Even if you don't use those batteries they would still die. The inverter will never be able to charge those batteries properly. They won't be able to give it proper absorption charge (14.4v at the very least) and 15.3v for 2 hours of equalisation at least once a month. You won't get that from your inverter. The charge controller is even worse. Fortunately you have a tubular battery so the situation can still be saveged. Get a different inverter one of the powerstar series from Must or felicity if possible, get a tracer series charge controller and connect your panels in series. All this would set u back over a 100k. It is the price for bad installation. Solar is not cheap. You can't afford to make a mistake because it gets even more expensive. |
| Re: Solar Energy, A Complement To FTA by kiekie1(m): 1:48pm On Jun 09, 2018 |
bigrovar:Happy weekend Bigrover . Nice points you made ! Its true most PWM controller isn't the best for flooded batteries , that's why I mostly prefer selling or using the a series ep solar mppt to tubular battery users as it has the ability to do upto 15v equalisation and user defined absorption/float settings.. NOTE: The only pwm cc i have seen trying on flooded batteries is the morningstar brand ![]() Smartcell global services 081-350-31951 |
| Re: Solar Energy, A Complement To FTA by Reprobate: 1:49pm On Jun 09, 2018 |
pls.a quick one. i hv 12v x 4 x 200ah batts and a 5kva 48v inverter.i also hv 1800w solar panel..hooked to a 60amp cc...i hv a function at my place..and want to power my 2hp ac on the inverter for 2 to 4hrs..its not such a sunny day so output from panels maybe low..say 600w/15amps..my batts are on float now..so cant tell what the panels will contribute if/when i power thr gen. so my question is. woyld running the 2hp split ac for 2 to 4hrs damage my batt bank?. would prefer 2 scenarios 1.zero input from panels 2.15a to 20amps input from panels |
| Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 2:04pm On Jun 09, 2018 |
2HP is about 1.5Kw - I have seen my own 2HP AC (Thermocool) draw as much as 2Kw when running because of additional components - blower fans e.t.c running. A 2kw load will flatten your 48v 200Ah battery bank within 4 to 5 hours max even with your panels adding extra juice of 600w as you said. Regardless, your batteries would recover even if they were drained low just once but definitely a C4 or C5 discharge rate is very bad for C20 rated batteries such as you likely have. More important is whether your 5Kva inverter can even bear the >2kw load at all? What make is the inverter? transformer based or transfornerless? Have you been using the 2HP AC on the inverter before now? I suggest you simply bypass the inverter and use your Gen to power your 2HP AC for this event/function at your place to avoid any regrets..... except you have been running the 2HP AC off the Inverter on a regular basis in the past? Reprobate: |
| Re: Solar Energy, A Complement To FTA by NiyiOmoIyunade(m): 2:09pm On Jun 09, 2018 |
Lolz @ ROY SOLAR, the solar charlatan's PWM CC of choice. Everywhere I see them I either replace with a proper CC or walk away if the client insists on using them. I can only imagine a few scenarios with very basic requirements where they could even work decently at all and most residential users do not fit in those scenarios. bigrovar: |
| Re: Solar Energy, A Complement To FTA by S007: 2:39pm On Jun 09, 2018 |
godspeed:Roy solar ke! You better remove that CC if you want to sleep well. I advice you contact the reputable suppliers here for good replacement. If possible, start your DIY from there. |
| Re: Solar Energy, A Complement To FTA by Reprobate: 2:45pm On Jun 09, 2018 |
NiyiOmoIyunade:thanks for the prompt response. yes i hv powered a normal 1.5hp ac + 1hp inverter ac simultaneously b4..inverter shows 61% load.. i couldnt wait and powered the 2hp ac..load displayed was 11% with only the indoor unit blowing..and jumped to 56% when the outdoor unit kicked in..battery voltage dropped from float of 58v to 50.8v..cc input is btw 550w to 650w..not a sunny day.. intend to keep an eye on the batt voltage..so it doesnt go below 48v...batts hv been having an easy life..never gone below 49.2v on normal use.its a highpower inverter |
| Re: Solar Energy, A Complement To FTA by godspeed: 4:02pm On Jun 09, 2018 |
bigrovar:Thanks bro In all honesty, deep down, I have always suspected the charge controller. I have no problems changing it if it is definitely it's the cause of the problem. Can I be sure I'll enjoy up to 15 hrs (the battery' s full charge capacity )if I get a new charge controller ? Which do you recommend ? Then, do I really also need to change the inverter too. I think the inverter is ok, it's one of the best out there for home use |
| Re: Solar Energy, A Complement To FTA by godspeed: 4:04pm On Jun 09, 2018 |
S007:Alright bro. Please which charge controller do u recommend, I mean, I need to get at least 80% charge on the battery daily. Which CC will serve me. |
| Re: Solar Energy, A Complement To FTA by kiekie1(m): 4:13pm On Jun 09, 2018 |
godspeed:You can keep your inverter . A series ep solar is very OK for 12/24v solar set up with tubular batteries and its readily available in 30 and 40 amps at affordable prices .. You can load upto 4 units of 300-340w pv modules on it if its installed in a well ventilated space . Cheer's |
| Re: Solar Energy, A Complement To FTA by JUO(m): 4:30pm On Jun 09, 2018 |
bigrovar:He needs a new charge controller contact us for 30a tracer CN series |
| Re: Solar Energy, A Complement To FTA by JUO(m): 4:36pm On Jun 09, 2018 |
Reprobate:This thing dey sweet you now, don't complain of battery failure after 13 months |