obimind:Your 150w panels would provide a current of about 8.89A each, if ur batteries are in series or parallels for either a 24v or 12v system, the charge controller would still be undersized. In series (24v) Then your panels would be connected in 2 strings, each having two panels. 8.89A(Isc) x 2 (strings) x 1.25 (safety factor) = 22.22A In parallel (12v) Then your panels would have to be connect in 4 strings, 8.89A(Isc) x 4 (strings) x 1.25 (safety factor) = 44.45A you are definitely under utilizing your panels, either way so u need to upgrade your charge controller. |