Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by mufutau55(op):
topsy23:
Pls let us be careful about our wiring of our project or house. Somebody called me on Monday to inspect an apartment in IKOYI , they have electrical issues and three of their AC's got burnt in the last four month. We went there and carry out power audit. We discovered that all the socket outlets and AC switches has no earth cable . We saw earth pit chamber within the compound and also 4mm green earth cable run from earth pit to only ground floor distribution and there is no continuation to the first floor distribution board. Anytime there is surge in that area definitely it will affect one or two things in the house and this surge normally occur when there is power supply from PHCN. We plugged electric kettle to one of the socket outlets, the body of the kettle conduct electricity. The electrician only earth the distribution and not the entire house . The body of kitchen , the washing machine and some other electrical appliances are conducting

TAKE NOTE OF THE ANALYSIS BELOW

Lighting
You can use RED and BLACK cable only, reason is because there is no earth terminal in most of the light fittings they produce nowadays

SOCKET
2.5mm RED, BLACK and use 1.5mm green as the earth cable. And remember the same number of coils of cable is require for this. I have seen messages t from people requesting for 2.5mm
Red 3coils
Black 2coils
No green ...
The quantities above is wrong and incomplete
A. The quantities of RED must be the same with quantities of BLACK because they are both running from the same DB to each socket. The only area where we normally have more RED. than BLACK is when we are doing cable for lighting. The reason is that neutral doesn't connected to switch except you want to use smart switch

B. Earth cable is missing.and earth cable must have the same quantities as RED and BLACK

AC
4mm RED, BLACK and 2.5mm GREEN. And they must all have the same quantities since the are to connect to distribution boards down the AC switch .

Also the main earth cable to building always depend on the size of load cable used

If your load cable is 16mm IEE permit 10mm to serve as your earth cable.

Most time your earth cable can serve as neutral ONLY IF your neutral fails . That's why it very important and necessary to earth your building ..

If your neutral fail and there is no earth cable to serve as neutral your voltage can go as high as 300V and witt thus high voltage alot of things will get damage

Pls always insist on earth cable especially for your
- SOCKET
-AC OUTLET AND AC SWITCHES
-COOKER SOCKET
Thanks for this useful information from the expert and a professional.

And Yes, I quoted the whole post for a reason; and for the importancy.

Hajji M.
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Beframia: 4:28am On Sep 02, 2023
Permit me to also quote the post.
Thanks Topsy23.

topsy23:
Pls let us be careful about our wiring of our project or house. Somebody called me on Monday to inspect an apartment in IKOYI , they have electrical issues and three of their AC's got burnt in the last four month. We went there and carry out power audit. We discovered that all the socket outlets and AC switches has no earth cable . We saw earth pit chamber within the compound and also 4mm green earth cable run from earth pit to only ground floor distribution and there is no continuation to the first floor distribution board. Anytime there is surge in that area definitely it will affect one or two things in the house and this surge normally occur when there is power supply from PHCN. We plugged electric kettle to one of the socket outlets, the body of the kettle conduct electricity. The electrician only earth the distribution and not the entire house . The body of kitchen , the washing machine and some other electrical appliances are conducting

TAKE NOTE OF THE ANALYSIS BELOW

Lighting
You can use RED and BLACK cable only, reason is because there is no earth terminal in most of the light fittings they produce nowadays

SOCKET
2.5mm RED, BLACK and use 1.5mm green as the earth cable. And remember the same number of coils of cable is require for this. I have seen messages t from people requesting for 2.5mm
Red 3coils
Black 2coils
No green ...
The quantities above is wrong and incomplete
A. The quantities of RED must be the same with quantities of BLACK because they are both running from the same DB to each socket. The only area where we normally have more RED. than BLACK is when we are doing cable for lighting. The reason is that neutral doesn't connected to switch except you want to use smart switch

B. Earth cable is missing.and earth cable must have the same quantities as RED and BLACK

AC
4mm RED, BLACK and 2.5mm GREEN. And they must all have the same quantities since the are to connect to distribution boards down the AC switch .

Also the main earth cable to building always depend on the size of load cable used

If your load cable is 16mm IEE permit 10mm to serve as your earth cable.

Most time your earth cable can serve as neutral ONLY IF your neutral fails . That's why it very important and necessary to earth your building ..

If your neutral fail and there is no earth cable to serve as neutral your voltage can go as high as 300V and witt thus high voltage alot of things will get damage

Pls always insist on earth cable especially for your
- SOCKET
-AC OUTLET AND AC SWITCHES
-COOKER SOCKET
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by folmus: 6:47am On Sep 02, 2023
topsy23:
Pls let us be careful about our wiring of our project or house. Somebody called me on Monday to inspect an apartment in IKOYI , they have electrical issues and three of their AC's got burnt in the last four month. We went there and carry out power audit. We discovered that all the socket outlets and AC switches has no earth cable . We saw earth pit chamber within the compound and also 4mm green earth cable run from earth pit to only ground floor distribution and there is no continuation to the first floor distribution board. Anytime there is surge in that area definitely it will affect one or two things in the house and this surge normally occur when there is power supply from PHCN. We plugged electric kettle to one of the socket outlets, the body of the kettle conduct electricity. The electrician only earth the distribution and not the entire house . The body of kitchen , the washing machine and some other electrical appliances are conducting

TAKE NOTE OF THE ANALYSIS BELOW

Lighting
You can use RED and BLACK cable only, reason is because there is no earth terminal in most of the light fittings they produce nowadays

SOCKET
2.5mm RED, BLACK and use 1.5mm green as the earth cable. And remember the same number of coils of cable is require for this. I have seen messages t from people requesting for 2.5mm
Red 3coils
Black 2coils
No green ...
The quantities above is wrong and incomplete
A. The quantities of RED must be the same with quantities of BLACK because they are both running from the same DB to each socket. The only area where we normally have more RED. than BLACK is when we are doing cable for lighting. The reason is that neutral doesn't connected to switch except you want to use smart switch

B. Earth cable is missing.and earth cable must have the same quantities as RED and BLACK

AC
4mm RED, BLACK and 2.5mm GREEN. And they must all have the same quantities since the are to connect to distribution boards down the AC switch .

Also the main earth cable to building always depend on the size of load cable used

If your load cable is 16mm IEE permit 10mm to serve as your earth cable.

Most time your earth cable can serve as neutral ONLY IF your neutral fails . That's why it very important and necessary to earth your building ..

If your neutral fail and there is no earth cable to serve as neutral your voltage can go as high as 300V and witt thus high voltage alot of things will get damage

Pls always insist on earth cable especially for your
- SOCKET
-AC OUTLET AND AC SWITCHES
-COOKER SOCKET
Thanks for the expert explanation!
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by kiekie1(m): 8:29am On Sep 02, 2023
SMARTCELL DISTILLED WATER & ELECTROLYTES NOW IN STOCK!!

We are still committed to giving you the best quality of distilled water in the industry...

Join us in our price slash promo .. We look forward to working with you

Distilled water 25 Litres = N10,000 PER 25L GALLON (Selling with free 25L black Gallon)(BUY 2 GALLONS & GET 5L FREE)

Distilled water 25 Litres = N12,000 PER 25L GALLON (Selling with free 25L white Gallon)(BUY 2 GALLONS & GET 5L FREE)

Distilled water 5 Litres = N2,500 (Selling with free 5L gallon) (PROMO: BUY 12 units get 2 free)

Distilled water 1 Litre (Dozen pack) = N6000 (PROMO: BUY 12 packs & get 1 free)

Hydrometer = N5,000

Electrolyte 5L = N4,000

Electrolyte 25 Litres = N15,000 (with free 25L Industrial Gallon) .. (BUY 2 GALLONS & GET 5L DISTILLED WATER FREE).

Electrolyte is mixture of sulfuric acid & distilled water having predefined specific gravity or concentration per mol. Smartcell electrolytes maintains 1.265 - 1.280 specific gravity range.

*Deionized H2O Analysis:
*TDS = 0 - 0007 ppm
*PH = 6.8 - 7.0

*APPLICATIONS:
Smartcell deionized water is free of toxins, microbes , pollutants and can be used for:

-Tubular battery periodic top up
- Skin care formulation
- Steam Iron
- Soap making
- Hand sanitizer production
- Cleaning services
- Laboratory
- Automotive radiator Cooling Systems
- Continuous positive airway pressure machines

We're open for dealership discussions. Feel free to reach us via contact details below

Warehouse Location: Winners estate, Abule-egba , Lagos (Estate is situated behind popular Solomon grace secondary schools ,off Abiodun Onitiri avenue) but can be dispatched to any state on buyers expense.

For further enquiry & purchase;
Contact,
Smartcell global services
CALL LINE::::: 081-350-31951
WHATSAPP::: 081-703-85620

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by AAMTiling(m): 8:37am On Sep 02, 2023
Happy New Month...

We're still available for all your tiles installation needs.
* Wall tiling
* Floor tiling
* Interior
* Exterior tiling
* Swimming pool tiling etc

Call or Whatsapp: O7068853073

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Geekop: 8:45am On Sep 02, 2023
Geekop:
Good afternoon sirs and mas.
Please what's the current price for Stone dust in Lagos??
Thank you.
Anyone please??
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by kiekie1(m): 8:49am On Sep 02, 2023
YOHAKO LITHIUM BATTERIES AVAILABLE!!!


Yohako 48v 15kwh ...... N1,800,000
Yohako 24v 5kwh .......... 850,000

Warranty: 5 yrs

For further enquiry & purchase;
Contact,
Smartcell global services
CALL LINE::::: 081-350-31951
WHATSAPP::: 081-703-85620

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by QSFemi(m): 8:50am On Sep 02, 2023
We're still waiting or our next clients.

Contact CHOICE COST CONSULT for for quantity surveying services, viz-a-viz

1) Bill of Quantities (Projected estimated cost of construction)
2) Materials and Labour Schedule (breakdown of cost of materials and labour respectively for your construction projects)
3) Valuation of ongoing construction works (know the cost of already existing or ongoing construction)
4) Bidding and Tendering for construction jobs (As a contractor bidding for jobs, you need competitive tender to win the job. Nobody can help you out except a quantity surveyor.
5) Pricing of blank/unpriced bill of quantities for tendering purposes.
6) Invitation, pre-qualification and selection of contractor based on suitable tendering procedure. Don't award your jobs to the least bidder bit the least responsive bidder. Be smart. Don't let contractors fool you.
7) Contract administration from inception to completion of your projects. (interpretation of conditions of contract is one of the duties of a smart quantity surveyor)
cool Preparation of both feasibility and viability studies (if you're engaging in a commercial construction works, know the payback period and rate of investment of your projects. Nobody does it better than a quantity surveyor.
9) Life cycle costing
10) Cost control
11) Cash flow forecasting
Etc

Contact us today.
Mobile no: 09012800750
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Santoirino(m): 9:01am On Sep 02, 2023
Contact me for professional painting and house cleaning services for houses,shops,flats,duplexs,shopping malls and churches at afforded price around nigeria. Try us today
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Abudu2000(m): 11:47am On Sep 02, 2023
good morning to you all and a happy new month. Are you planning your retirement now, what real estate infrastructure do you have on ground now that you still have the strength to work and earn. if you dont have an answer to the question then now may just be the time to start up something that will secure your future and that of your descendants.

FOR YOUR ARCHITECTURAL DESIGN AND BUILDING CONSTRUCTION SEND ME A MESSAGE VIA WHATSAPP NO ON MY PROFILE

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by EsgeeTech7(m): 3:36pm On Sep 02, 2023
We are still your plug for all your roofing needs 09035076732,08078696012 esgeetechconcepts@gmail.com

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Horlardorjah(m): 4:49pm On Sep 02, 2023
Reeefe:
Good day house . has anyone done a roofing job before with a room in the roof sitting on the wooden tie beam. the king post is 16ft high. owner needs a 10x12 room in the roof.
What precisely do you need info on?
Do u need a roofer or u need the choice of materials to use for the floor.
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Philipok: 5:03pm On Sep 02, 2023
Ur Best art work designer still available for ur urgent delivery,09058432795.

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by oduncojamaica(m): 5:26pm On Sep 02, 2023
topsy23:
Pls let us be careful about our wiring of our project or house. Somebody called me on Monday to inspect an apartment in IKOYI , they have electrical issues and three of their AC's got burnt in the last four month. We went there and carry out power audit. We discovered that all the socket outlets and AC switches has no earth cable . We saw earth pit chamber within the compound and also 4mm green earth cable run from earth pit to only ground floor distribution and there is no continuation to the first floor distribution board. Anytime there is surge in that area definitely it will affect one or two things in the house and this surge normally occur when there is power supply from PHCN. We plugged electric kettle to one of the socket outlets, the body of the kettle conduct electricity. The electrician only earth the distribution and not the entire house . The body of kitchen , the washing machine and some other electrical appliances are conducting

TAKE NOTE OF THE ANALYSIS BELOW

Lighting
You can use RED and BLACK cable only, reason is because there is no earth terminal in most of the light fittings they produce nowadays

SOCKET
2.5mm RED, BLACK and use 1.5mm green as the earth cable. And remember the same number of coils of cable is require for this. I have seen messages t from people requesting for 2.5mm
Red 3coils
Black 2coils
No green ...
The quantities above is wrong and incomplete
A. The quantities of RED must be the same with quantities of BLACK because they are both running from the same DB to each socket. The only area where we normally have more RED. than BLACK is when we are doing cable for lighting. The reason is that neutral doesn't connected to switch except you want to use smart switch

B. Earth cable is missing.and earth cable must have the same quantities as RED and BLACK

AC
4mm RED, BLACK and 2.5mm GREEN. And they must all have the same quantities since the are to connect to distribution boards down the AC switch .

Also the main earth cable to building always depend on the size of load cable used

If your load cable is 16mm IEE permit 10mm to serve as your earth cable.

Most time your earth cable can serve as neutral ONLY IF your neutral fails . That's why it very important and necessary to earth your building ..

If your neutral fail and there is no earth cable to serve as neutral your voltage can go as high as 300V and witt thus high voltage alot of things will get damage

Pls always insist on earth cable especially for your
- SOCKET
-AC OUTLET AND AC SWITCHES
-COOKER SOCKET
Future reference
Thanks
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by topsy23(m): 5:28pm On Sep 02, 2023
oduncojamaica:
Future reference
Thanks
You are welcome sir
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by topsy23(m): 5:28pm On Sep 02, 2023
mufutau55:
Thanks for this useful information from the expert and a professional.

And Yes, I quoted the whole post for a reason; and for the importancy.

Hajji M.
Thank you sir.
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by topsy23(m): 9:17pm On Sep 02, 2023
topsy23:
Good afternoon to everyone. Nigerchin cable manufacturer release their new price list this week and percentage increase is about 35% for the single core cables. Remember the notification was sent 3 weeks before the implementation of the new price.

Now other cable manufactures are ready to follow the same procedure now since all of them are importing raw materials from oversea. Things are not working normal in this country. Imagine 35% increase and there is no regulatory body controlling price in this country of ours. God will help us . .

My Advice to people now is that if you have the opportunity to buy your cable and keep pls quickly do before others increase their price.

Coleman
Wichtech
and other are yet to communicate their new price to distributors.

Thanks
Pls take Note of this
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Adedward(m): 10:04pm On Sep 02, 2023
GOOD EVENING HOUSE, ADEDWARD, ADEDWARD, ADEDWARD, WE ARE SET TO FILL THIS PROJECT WITH CASEMENT WINDOWS AND SLIDING WINDOWS WITHOUT BURGLARIES,

LOCATION ,IBEJU LEKKI
COLOR OF MATERIAL GREY COLOR
5 MM BLACK GLASS,

CONTACT ADEDWARD FOR UR WINDOWS THANKS U,

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by uncleteeh(m): 10:31pm On Sep 02, 2023
Reeefe:
😆 I'm the contractor/ engineer on site. the guys are stressing me already. I'm changing the arrangements soon because of the raining season
Okay.
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Reeefe(m): 10:56pm On Sep 02, 2023
Horlardorjah:
What precisely do you need info on?
Do u need a roofer or u need the choice of materials to use for the floor.
was wondering why no 1 is doing it. and if anyone has n can work me through
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by MRFIXER001: 12:07am On Sep 03, 2023
Great explanation
topsy23:
Pls let us be careful about our wiring of our project or house. Somebody called me on Monday to inspect an apartment in IKOYI , they have electrical issues and three of their AC's got burnt in the last four month. We went there and carry out power audit. We discovered that all the socket outlets and AC switches has no earth cable . We saw earth pit chamber within the compound and also 4mm green earth cable run from earth pit to only ground floor distribution and there is no continuation to the first floor distribution board. Anytime there is surge in that area definitely it will affect one or two things in the house and this surge normally occur when there is power supply from PHCN. We plugged electric kettle to one of the socket outlets, the body of the kettle conduct electricity. The electrician only earth the distribution and not the entire house . The body of kitchen , the washing machine and some other electrical appliances are conducting

TAKE NOTE OF THE ANALYSIS BELOW

Lighting
You can use RED and BLACK cable only, reason is because there is no earth terminal in most of the light fittings they produce nowadays

SOCKET
2.5mm RED, BLACK and use 1.5mm green as the earth cable. And remember the same number of coils of cable is require for this. I have seen messages t from people requesting for 2.5mm
Red 3coils
Black 2coils
No green ...
The quantities above is wrong and incomplete
A. The quantities of RED must be the same with quantities of BLACK because they are both running from the same DB to each socket. The only area where we normally have more RED. than BLACK is when we are doing cable for lighting. The reason is that neutral doesn't connected to switch except you want to use smart switch

B. Earth cable is missing.and earth cable must have the same quantities as RED and BLACK

AC
4mm RED, BLACK and 2.5mm GREEN. And they must all have the same quantities since the are to connect to distribution boards down the AC switch .

Also the main earth cable to building always depend on the size of load cable used

If your load cable is 16mm IEE permit 10mm to serve as your earth cable.

Most time your earth cable can serve as neutral ONLY IF your neutral fails . That's why it very important and necessary to earth your building ..

If your neutral fail and there is no earth cable to serve as neutral your voltage can go as high as 300V and witt thus high voltage alot of things will get damage

Pls always insist on earth cable especially for your
- SOCKET
-AC OUTLET AND AC SWITCHES
-COOKER SOCKET
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by DFAMEGUY11S(m): 4:27am On Sep 03, 2023
Good morning my people of Nairaland customer and friends I greet you all.

Osinachiadima global enterprise
Rockhome global Enterprise
Dealer of all kinds of building materials such as:
Spanish tiles
Indian tiles
Italian tiles
China tile
Nigeria tile
Bricks tiles
Sanitary
Doors
Etc
Contact : 07087953771 or 07046234748
Email: osinachicolins20@gmail.com

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Philipok: 8:01am On Sep 03, 2023
Contact me for ur polystyrene and artwork design.08165523784.

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by kkonsults: 8:13am On Sep 03, 2023
Contact us for your Architectural Designs

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by olaitoro(m): 8:24am On Sep 03, 2023
topsy23:
Pls let us be careful about our wiring of our project or house. Somebody called me on Monday to inspect an apartment in IKOYI , they have electrical issues and three of their AC's got burnt in the last four month. We went there and carry out power audit. We discovered that all the socket outlets and AC switches has no earth cable . We saw earth pit chamber within the compound and also 4mm green earth cable run from earth pit to only ground floor distribution and there is no continuation to the first floor distribution board. Anytime there is surge in that area definitely it will affect one or two things in the house and this surge normally occur when there is power supply from PHCN. We plugged electric kettle to one of the socket outlets, the body of the kettle conduct electricity. The electrician only earth the distribution and not the entire house . The body of kitchen , the washing machine and some other electrical appliances are conducting

TAKE NOTE OF THE ANALYSIS BELOW

Lighting
You can use RED and BLACK cable only, reason is because there is no earth terminal in most of the light fittings they produce nowadays

SOCKET
2.5mm RED, BLACK and use 1.5mm green as the earth cable. And remember the same number of coils of cable is require for this. I have seen messages t from people requesting for 2.5mm
Red 3coils
Black 2coils
No green ...
The quantities above is wrong and incomplete
A. The quantities of RED must be the same with quantities of BLACK because they are both running from the same DB to each socket. The only area where we normally have more RED. than BLACK is when we are doing cable for lighting. The reason is that neutral doesn't connected to switch except you want to use smart switch

B. Earth cable is missing.and earth cable must have the same quantities as RED and BLACK

AC
4mm RED, BLACK and 2.5mm GREEN. And they must all have the same quantities since the are to connect to distribution boards down the AC switch .

Also the main earth cable to building always depend on the size of load cable used

If your load cable is 16mm IEE permit 10mm to serve as your earth cable.

Most time your earth cable can serve as neutral ONLY IF your neutral fails . That's why it very important and necessary to earth your building ..

If your neutral fail and there is no earth cable to serve as neutral your voltage can go as high as 300V and witt thus high voltage alot of things will get damage

Pls always insist on earth cable especially for your
- SOCKET
-AC OUTLET AND AC SWITCHES
-COOKER SOCKET
Thanks Engr, bookmarked this already
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by bolu1986(m): 8:35am On Sep 03, 2023
Good morning to you all and happy new week


07088534661 WhatsApp

Let’s handle your pop & wall screeding

Timely delivery.

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by topsy23(m): 12:02pm On Sep 03, 2023
olaitoro:
Thanks Engr, bookmarked this already
You are welcome sir
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by twinskenny(m): 12:37pm On Sep 03, 2023
Cc Gbadexy please what kind of paint is this

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by gbadexy(m): 1:53pm On Sep 03, 2023
twinskenny:
Cc Gbadexy please what kind of paint is this
It's not too clear. It looks like marble effect.

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by topsy23(m): 3:20pm On Sep 03, 2023
Beframia:
Permit me to also quote the post.
Thanks Topsy23.
Permission granted sir
Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by Philipok: 7:34pm On Sep 03, 2023
Updated art work 08165523784.

Re: General Topic Thread-To Discuss Anything And Everything in Building Construction by kiekie1(m): 7:27am On Sep 04, 2023
WE BUY DEAD/SCRAP BATTERIES!!!

We also buy off scrap/dead deep cycle batteries from any state to Lagos (Terms & Condition applies) ..

You could make money from your dead or swollen batteries.


12v 200a ..... N30,000
12v 150a.......N22,000
12v 100a.......N14,000
2v 500a ........N7,000

Free pickup within some parts of Lagos mainland whist Shared cost logistics within Lagos Island environs . . If outside Lagos state , send the scrap batteries to your nearby Lagos park & get your payment alert immediately after confirmatory remarks from me with the transport company manager / secretary or driver shared logistics cost depending on scrap battery quantity) ..

Scrap batteries could also be traded in for brand new battery replacements.. Prices might be reviewed from time to time


Contact,
Smartcell global services
CALL LINE::::: 081-350-31951
WHATSAPP::: 081-703-85620

1 2 3 ... 3462 3463 3464 3465 3466 3467 3468 ... 3990 Reply

Discuss Anything Property And Lets Make Money In The ProcessResidential Building Construction Mistakes In Nigeria You Need To AvoidGeneral Topic Thread - The Roforofo Thread Of Construction Activities234

Viewing this topic: 3 guest(s)